5.3  Configure low charger alarm  
An alarm displays on the LCD when Low Charger Alarm is enabled and the voltage from the charger is 
0.4 volts below the battery voltage. If Low Charger Alarm is disabled, the alarm does not display. 
Low Charger Alarm State is read-only and displays the current state: Not in Alarm, or In Alarm. 
To enable the alarm: 
1.  Launch PCCU and click View on the menu bar. Then click Expert to enter Expert view. 
2.  Click the station ID (the top item on the navigation tree) to display the Station Setup screen. 
Scroll down to the Low Charger Alarm Enable section (Figure 5-3
). Click the Low Charger Alarm 
Value column and select Enabled from the drop-down list. 
Figure 5-3: Low charger alarm 
3.  Click Send. 
 
5.4  Customize the LCD display  
The maximum number of characters per row on the display is 21 (X location with a range 0 to 20). 
The size of a character is 8 x 6 pixels. 
The maximum number of lines on the display is 8 (Y location). Lines 3 and 6 are separator lines. Lines 
7 and 8 are reserved for the annunciators. Two pairs of lines are reserved for the display items with 
data, units, annunciators, and plot (optional): lines 1 (Y=0), 2 (Y=1), and 4 (Y=0), 5 (Y=1). For both 
pairs, the top line has a Y location of 0. The second line has a Y location of 1. These locations indicate 
position relative to the pair, not the entire height of the LCD (Figure 5-4
). 
Figure 5-4: LCD display items 
During operation, the LCD continuously scrolls through the operating parameters. Table 5-1
 shows the 
parameters that typically display. The display is customizable. 
Table 5-1: RMC display item options 
Yesterday’s Percent DP 
Low Limit 
Percent time below DP Low Set Point 
Yesterday’s Percent DP 
High Limit 
Percent time above DP High Set Point 
LINE 1
LINE 2
LINE 3
LINE 4
LINE 5
LINE 6
LINE 7
LINE 8
(Y) 0
(Y) 1
(Y) 0
(Y) 1
(X)0…………………………………………Characters…………………………………...….19     20  
NAME
DATA      UNITS
NAME
DATA      UNITS
A2 A3 A4 A5 A6 A7 A8A1