EasyManuals Logo

ABB RMC-100 User Manual

ABB RMC-100
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #103 background imageLoading...
Page #103 background image
2105552MNAE | RMC-100 | 103
Figure 6-3: Station Setup tab Security switch status
6. Type a four-digit security code into Security Code Level 1 (Level 1 access grants read only
access to the device).
7. Type a four-digit security code for Security Code Level 2 (Level 2 access grants read and write
access to the device).
IMPORTANT NOTE: Record the security codes. They are not visible on the Station Setup tab after
you save them.
8. Click Send.
9. On the RMC, set the security switch to ON.
10. On the Station Setup tab, click Re-read. Verify that the security switch status is On.
Enforcement of the security codes is in effect.
IMPORTANT NOTE:
PCCU32 requires the security codes the next time it attempts to connect to
the device.
The security codes in PCCU32 version 7.57
or later or in WinCCU do not prevent MODBUS® access
to the RMC.
6.6 Configure Role-Based Access Control (RBAC)
Role Based Access Control (Role Based Access Control, RBAC) is a feature within PCCU32 that allows
an administrator to designate roles and control access levels to various applications and processes in
the flow computer. The G5 and newer flow computers and NGC devices support RBAC security files.
Each security file is configurable for the specific device type.
When designing an RBAC security system, consider all required user-access to the system. Create the
users and an administrator and assign a default role to each.
RBAC security configuration restricts or disables any unapproved applications and functions for the
current user. Restricted applications and restricted functions are not visible on the PCCU32 navigation
tree. The Send button is also grayed out on applications with read-only functionality.

Table of Contents

Other manuals for ABB RMC-100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RMC-100 and is the answer not in the manual?

ABB RMC-100 Specifications

General IconGeneral
Product Type DesignationRMC-100
Rated Voltage24 V DC
Output Voltage24 V DC
Protection ClassIP20
Weight0.3 kg
Input Voltage24 V DC
Humidity5 ... 95% RH, non-condensing