2105552MNAE | RMC-100 | 129
Figure 7-2: AI 1 set to voltage mode
4. Turn on the calibrator.
5. Click the Calibrate icon on the PCCU toolbar. The calibration Checks screen displays with a
request to take an application out of hold (Figure 7-3
). This example shows the request for
AGA3-2.
The calibration mode automatically places active measurement applications
on hold. This is not required for I/O calibration. The calibration navigation tree in
Figure 7-3 shows
four AGA3 applications. The checkmark indicates that they are all in Hold mode. Pop
-ups display to
remove applications from hold. Accept them all. These requests display one at a time
until the last
application is out of hold.