Figure 7-25: Low calibration value entry
16. Adjust the calibrator to apply the low value of the signal range. For example, if the signal range
of the external device is 4 to 20 mA, apply 4 mA.
17. Observe the value in the Current Reading field (Figure 7-26
). The expected voltage value for a
4 mA input is approximately 1 Vdc (0.004 * 250 = 1 Vdc).
18. Accept the default low range value of 0.