85SCU200 INSITE ENERGY MANAGEMENT SYSTEM
Meter address [0x25]
Unique meter ID from which frame was available in M-Bus data registers. It is automatically updated after
read from M-Bus data registers, with next meter ID if at least one is available in device queue.
Meter ID Manufacturer Version Meter type
4 bytes 2 bytes 1 byte 1byte
M-Bus data [0x29]
These registers holds entire Wireless M-Bus frame, decrypted but not decapsulated. Further
decapsulation and processing of this raw data is required to extract necessary information, according to
Wireless M-Bus protocol specification. Read of these registers, cause update and load of next frame from
device queue if at least one is available.
M-Bus data rest [0xA2]
These registers holds rest of Wireless M-Bus frame if frame cannot fit in base M-Bus data registers.
For explanation of format of M-Bus data refer to European standard documentation EN 13757-3:2018
Chapter 6.
Software reset [0x200]
This register is write only, and writing special code into this register cause restart of device. This code
value is 0xB4B4.
Factory reset [0x201]
This register is write only. Writing special code into this register cause factory defaults to be restored.
This code value is 0xA1A1
Also all meter keys stored in module will be deleted
Setting Default value
ModbusID 247
WMBus mode T
WMBus antenna 0 ( internal )