EasyManua.ls Logo

ABB Zenith ZBTS T Series - Page 32

ABB Zenith ZBTS T Series
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
Zenith ZBTS T-series 100-1200A, INSTALLATION AND OPERATING INSTRUCTION
1
3.3.1.3 Main Menu
Fig. 3.13 By touching on Start Menu lower left corner
-image you can move to the Main Menu page of
Operation, Parameters, Measurements, Settings, Test
and About, see the table below for the selections
TruONE ATS
Overviews
Main Menu Measures
Analog Meters
Overviews
Switch Overview
Operation Parameters Measurements
AboutTestSettings
TruONE ATS
Notice
When you have changed the parameter, go
always back in the menu and confirm the
change always when asked.
Notice
The default values are marked in the menu
tree by *-marking.
NOTE! Setting the switch to AUTO mode:
MAIN MENU –> Operation –> Operation
Mode –> AUTO, see the table on next
page.
Operation modes:
Bypass switch default settings:
MAN permanent
ATS switch default settings:
MAN momentary
NOTE! If the switch is controlled with the
HMI keys I-O-II, the switch mode automat-
ically switches to MAN momentary mode.
NOTE! See the "BASIC OPERATION IN-
STRUCTION" on the door of Bypass-Isola-
tion Automatic Transfer Switch and more
detailed information from chapter 3.4
"Description of Basic Functionality".
When connecting the Bypass-Isolation
Automatic Transfer Switch to operation
the Operation modes of the switches
have to set:
In ATS HMI operations menu, set ATS to
AUTO mode.
In Bypass HMI operations menu, set By-
pass switch to MAN Permanent mode.

Table of Contents

Related product manuals