Operation *Default
Alarm Reset Reset any active switch control alarms (open I failure, close I failure, open II
failure, close II failure)
Bypass Time Delay
Bypass any currently running time delay
HMI Control Keys
Enabled*
Disabled
Energy Counters Reset energy values
Operation mode
AUTO* Automatic switch control mode.
MAN momentary Manual operation mode but warning that
device is in manual mode will be shown by
HMI. ATS will automatically send and
remove the generator start signal but user
intervention is required to initiate transfer
and retransfer.
MAN permanent Manual operation mode but no manual
mode warnings are shown by HMI. ATS will
automatically send and remove the
generator start signal but user
intervention is required to initiate transfer
and retransfer.
MAN retransfer Same as AUTO but automatic retransfer
sequence is disabled. Load will be kept on
non-priority source until operator
manually (by HMI or manual handle) or
remotely operates the load back to
priority source.