EVO 150 Controller
33
INHIBIT and AUXILIARY Input Configuration
This parameter swaps the function of the INHIBIT and AUXILIARY inputs. This is useful when
your application requires either a non-isolated AUXILIARY input, or an opto-isolated INHIBIT
input.
7 2 0
The INHIBIT function is routed through J8 terminal 1 (non-isolated).
The AUXILIARY function is routed through the PLC I/O board, J1
terminal 8 (opto-isolated).
This is the default setting.
7 2 1
The INHIBIT function is routed through the PLC I/O board, J1 terminal 8
(opto-isolated).
The AUXILIARY function is routed through J8 terminal 1 (non-isolated).
Parameter 73 is reserved for future use.
Sensor A Transducer Orientation
This parameter reverses the order of the transducer beams in Sensor A.
7 4 0
This is the default setting. Beam 1 is located at the end of the
transducer closest to the pigtail wiring.
7 4 1
Beam 1 is located at the end of the transducer farthest from the pigtail
wiring.
Sensor B Transducer Orientation
This parameter reverses the order of the transducer beams in Sensor B.
7 5 0
This is the default setting. Beam 1 is located at the end of the
transducer closest to the pigtail wiring.
7 5 1
Beam 1 is located at the end of the transducer farthest from the pigtail
wiring.
Sensor A Reduced Length
7 6 2
This parameter is used to reduce the sensing area of WideArray senso
r
A by establishing the number of active beams. As the value of this
parameter is lowered the low-numbered beams will be deactivated first,
beginning with beam 1. The minimum value for WideArray sensors is 4.
The minimum value for PointSource sensors is 2. The maximum value is
determined by parameter 24. The default value is 2.
Range: 2 to 128
Note: Parameter 24 must always be set to the actual full length of sensor A.