EVO 150 Controller
34
Sensor B Reduced Length
7 7 2
This parameter is used to reduce the sensing area of WideArray senso
r
B by establishing the number of active beams. As the value of this
parameter is lowered the low-numbered beams will be deactivated first,
beginning with beam 1. The minimum value for WideArray sensors is 4.
The minimum value for PointSource sensors is 2. The maximum value is
determined by parameter 25. The default value is 2.
Range: 2 to 128
Note: Parameter 25 must always be set to the actual full length of sensor B.
Fieldbus Swap Bytes
This parameter swaps the high and low bytes of all fieldbus input and output data words.
7 8 0
The data bytes are not swapped.
7 8 1
This is the default setting. The data bytes are swapped.
Parameters 79 through 83 have not yet been implemented.
Maximum Motor Current
8 3 1 5
This parameter is used to adjust the available amperage provided to the
actuator motor. The default value is 15.
Range: 1 to 30
Motor Direction Byte
This parameter swaps the direction of the motor.
8 4 0
The motor direction is inverted.
8 4 1
This is the default setting. The motor direction is not inverted.
Caution: This parameter is intended to be used for non-typical linear actuators. DO NOT
use this parameter to change motor direction on standard systems!
Fieldbus Enable Bit
This parameter enables operation for the optional fieldbus card.
8 5 0
This is the default setting. The field bus is not enabled.
8 5 1
The field bus is enabled.
Note: The optional serial I/O board will not operate when the field bus is enabled.