! Important Programming Notes !
To use the advanced features of the new Chelsea Digital Switch, please ensure the
following:
Always set a Chelsea Digital Switch as a “14 Button Switch” in the Panel/Switch
Types screen. This is true even if the switch only has 1, 2 or 3 physical buttons.
The reason for this is because advanced programming requires setting parameters
for buttons 7-14, even though they are “virtual” buttons and not physically present
on the switch.
To access advanced programming functions of the Chelsea Switch, you must have
DTC clock version 4.48 or later.
To use advanced programming functions of the Chelsea Switch, you must be
using switch firmware 1.12 or later. The version of firmware a switch has is
displayed in the lower left corner of the SETUP screen for that switch.