EasyManuals Logo

Acuity Controls GR2400 User Manual

Acuity Controls GR2400
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
! Important Programming Notes !
To use the advanced features of the new Chelsea Digital Switch, please ensure the
following:
Always set a Chelsea Digital Switch as a “14 Button Switch” in the Panel/Switch
Types screen. This is true even if the switch only has 1, 2 or 3 physical buttons.
The reason for this is because advanced programming requires setting parameters
for buttons 7-14, even though they are “virtual” buttons and not physically present
on the switch.
To access advanced programming functions of the Chelsea Switch, you must have
DTC clock version 4.48 or later.
To use advanced programming functions of the Chelsea Switch, you must be
using switch firmware 1.12 or later. The version of firmware a switch has is
displayed in the lower left corner of the SETUP screen for that switch.
- 2 -
86

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Acuity Controls GR2400 and is the answer not in the manual?

Acuity Controls GR2400 Specifications

General IconGeneral
BrandAcuity Controls
ModelGR2400
CategoryRelays
LanguageEnglish