Table 2.2
LED logic for other buttons
Sets the logic which determines if the Status LED over each of the switch’s
buttons should be on or off. This field applies to buttons in TOGGLE MODE,
ON MODE, MAINTAIN, MIX MODE (all other settings except OFF MODE).
Possible Values Result
AND The Status LED on a button will light up only if ALL the
controlled relays are ON. In MIX MODE the LED will be
lit only if ALL the controlled relays are in the state (ON or
OFF) the button was programmed to set them to. (This is
also called “True” switch logic. It is usually used for MIX
MODE or OFF MODE buttons.)
OR The Status LED on a button will light up if ONE OR
MORE of the controlled relays are ON. In MIX MODE
the LED will be lit if ONE OR MORE of the controlled
relays are in the state (ON or OFF) the button was
programmed to set them to. (Usually this logic in used for
buttons that are set to something other than MIX MODE or
OFF MODE).
OR-INVERT The Status LED on a button will light up only if NONE of
the controlled relays are ON (i.e., they are all OFF). In
MIX MODE the LED will be lit only if NONE of the
controlled relays are in the state (ON or OFF) the button
was programmed to set them to (they must all be in the
opposite state from what the button was assigned to set
them to).
AND-INVERT The Status LED on a button will light up only if ONE OR
MORE of the controlled relays are OFF. In MIX MODE
the LED will be lit only if ONE OR MORE of the
controlled relays are in the opposite state from what the
button was programmed to set them to.
BACK TO PAGE 1
To go back to the first page of switch setup options, highlight the field “BACK
TO PAGE 1” and press ENTER.