ADAM-4000 Series User Manual 96
$AA6 Read Channel Status
Get the enable/disable status of all
channels in an analog module
5-18
$AA0Ci
Single Channel
Span Calibration
Calibrates a specified channel to cor-
rect for gain errors
5-27
$AA1Ci
Single Channel
Offset Calibration
Calibrates a specified channel to cor-
rect for offset errors
5-28
$AA7CiRrr
Single Channel
Range Configuration
Configure the input type and range of
the specified channel in an analog
input module
5-29
$AA8Ci
Read Single Chan-
nel Range Configura-
tion
Get the input type and range of the
specified channel in an analog input
module
5-30
$AAXnnnn
Watchdog Timer
Setting
Set communication WDT cycle time
from 0000 ~ 9999 (unit: 0.1 second. if
value is 0000, the communication
WDT function will be disable)
5-31
$AAY
Read Watchdog
Timer Setting
Read the cycle time setting of com-
munication WDT
5-32
Table 4.9: ADAM-4017+ Input range and external calibrating input
source for each input type
Range
bcode(Hex)
Input Range Max. Signal Min Signal
Displayed
Resolution
07 4~20 mA +20.000 +4.000 1 uA
08 +/-10 V +10.000 -10.000 1mV
09 +/-5 V +5.0000 -5.0000 100.00uV
0a +/-1 V +1.0000 -1.0000 100.00uV
0b +/-500 mV +500.00 -500.00 10uV
0c +/-150 mV +150.00 -150.00 10uV
0d +/-20 mA +20.000 -20.000 1uA
Table 4.8: ADAM-4017+ Command Table