ADAM-4000 Series User Manual 294
Table A.10: ADAM-4018/4018+ Range Accuracy for Thermocouple
Range Code (Hex) Input Range Typical Accuracy Maximum Error Units
0E
J thermocouple
0 to760 °C
±1.0 ±1.5 °C
0F
K thermocouple
0 to 1370 °C
±1.0 ±1.5 °C
10
T thermocouple
-100 to 400 °C
±1.0 ±1.5 °C
11
E thermocouple
0 to 1000 °C
±1.0 ±1.5 °C
12
R thermocouple
500 to 1750 °C
±1.2 ±2.5 °C
13
S thermocouple
500 to 1750 °C
±1.2 ±2.5 °C
14
B thermocouple
500 to 1800 °C
±2.0 ±3.0 °C
Note! Because the CJC sensor of ADAM-4018 is located in the side of chan-
nel 0 to 4, the measurement will have the difference ± 1 °C between
channel 0 ~ 4 and channel 5 ~ 7.