2–9Troubleshooting and Error Codes
Publication 1336 IMPACT-6.2 – March 1998
Fault Code and
Text
Suggested ActionDescription
Fault
Type
LED Information
06042
SP 2 Timeout
VP, Flashing red Soft
The SCANport adapter at port 2 has been
disconnected and the logic mask bit for
port 2 is set (1).
If the adapter was not intentionally
disconnected:
Check the wiring to the SCANport adapters.
Replace wiring, SCANport expander,
SCANport adapters, and main control board.
Replace drive, if required.
If you do not want this condition to be
reported as a fault, change bit 10 in Fault
Select 1 (parameter 20) to 0.
06043
SP 3 Timeout
VP, Flashing red Soft
The SCANport adapter at port 3 has been
disconnected and the logic mask bit for
port 3 is set (1).
If the adapter was not intentionally
disconnected:
Check the wiring to the SCANport adapters.
Replace wiring, SCANport expander,
SCANport adapters, and main control board.
Replace drive, if required.
If you do not want this condition to be
reported as a fault, change bit 11 in Fault
Select 1 (parameter 20) to 0.
06044
SP 4 Timeout
VP, Flashing red Soft
The SCANport adapter at port 4 has been
disconnected and the logic mask bit for
port 4 is set (1).
If the adapter was not intentionally
disconnected:
Check the wiring to the SCANport adapters.
Replace wiring, SCANport expander,
SCANport adapters, and main control board.
Replace drive, if required.
If you do not want this condition to be
reported as a fault, change bit 12 in Fault
Select 1 (parameter 20) to 0.
06045
SP 5 Timeout
VP, Flashing red Soft
The SCANport adapter at port 5 has been
disconnected and the logic mask bit for
port 5 is set (1).
If the adapter was not intentionally
disconnected:
Check the wiring to the SCANport adapters.
Replace wiring, SCANport expander,
SCANport adapters, and main control board.
Replace drive, if required.
If you do not want this condition to be
reported as a fault, change bit 13 in Fault
Select 1 (parameter 20) to 0.
06046
SP 6 Timeout
VP, Flashing red Soft
The SCANport adapter at port 6 has been
disconnected and the logic mask bit for
port 6 is set (1).
If the adapter was not intentionally
disconnected:
Check the wiring to the SCANport adapters.
Replace wiring, SCANport expander,
SCANport adapters, and main control board.
Replace drive, if required.
If you do not want this condition to be
reported as a fault, change bit 14 in Fault
Select 1 (parameter 20) to 0.
06047
SP Error
VP, Flashing red Soft
SCANport communications have been
interrupted.
If the adapter was not intentionally
disconnected:
Check the amount of noise on the system.
Check the wiring to the SCANport adapters.
Replace wiring, SCANport expander,
SCANport adapters, and main control board.
Replace drive, if required.
If you do not want this condition to be
reported as a fault, change bit 15 in Fault
Select 1 (parameter 20) to 0.

Table of Contents

Other manuals for Allen-Bradley 1336 PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1336 PLUS and is the answer not in the manual?

Allen-Bradley 1336 PLUS Specifications

General IconGeneral
Input Voltage200-240VAC, 380-480VAC, 500-600VAC
Output Frequency0-400 Hz
Frequency50/60 Hz
DimensionsVaries by model
WeightVaries by model
EnclosureNEMA 1
Output CurrentVaries by model
Power RatingVaries by model
CommunicationRS-485
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Storage Temperature-40 to 70°C (-40 to 158°F)
Humidity5 to 95% non-condensing
Control MethodSensorless Vector