Rockwell Automation Publication 1444-UM001D-EN-P - June 2018 281
Operate the Module Chapter 10
Example 2
Table 63 - 3 Channels; Alert, Danger, TX Fault; Trip on Alarm 0 Danger
Dynamic Alignment Static Alignment
Voted Alarm 0: Actuate on Alert, Danger, TX Fault Voted Alarm 0: Actuate on Danger
Voted Alarm 1: Actuate on Alert, Danger, TX Fault Voted Alarm 1: Actuate on Danger
Voted Alarm 2: Actuate on Alert, Danger, TX Fault Voted Alarm 2: Actuate on Danger
Voted Alarms 3 …12: Not enabled Voted Alarm 3: Actuate on Alert
Voted Alarm 4: Actuate on Alert
Voted Alarm 5: Actuate on Alert
Voted Alarm 6: Actuate on TX Fault
Voted Alarm 7: Actuate on TX Fault
Voted Alarm 8: Actuate on TX Fault
Voted Alarms 9 …12: Not enabled
Relay = Voted Alarm 0, on Danger Relay = Voted Alarm 0, on Danger
Relay Assigned Output; R = Reserved; NA = Not Allocated; TXF = Transducer Fault
Voted Alarm Instance Voted Alarm Status
Alarm
Status #
0123Voted
Alarm#
01Status to Activate
On
0 1000 0 01 2Danger
1 1000 0 10 1Alert
2 1000 0 11 3TXF
3 0100 1 10 1Alert
4 0100 1 01 2Danger
5 0100 1 11 3TXF
6 1100 2 10 1Alert
7 1100 2 01 2Danger
8 1100 2 11 3TXF
9…12 0000 NA 00 0
Voted Alarm Instance Voted Alarm Status
Alarm
Status #
0123Voted
Alarm#
01Status to Activate
On
0 1000 0 01 2Danger
1 0100 1 01 2Danger
2 1100 2 01 2Danger
3 0010 3 10 1Alert
4 1010 4 10 1Alert
5 0110 5 10 1Alert
6 1110 6 11 3TXF
7 0001 7 11 3TXF
8 1001 8 11 3TXF
9 …12 0000 NA 00 0