282 Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Chapter 10 Operate the Module
Example 3
Table 64 - 4-Channels; Alert and Danger; Expansion Relays
Dynamic Alignment Static Alignment
Voted Alarm 0: Actuate on Alert, Danger Voted Alarm 0: Actuate on Danger
Voted Alarm 1: Actuate on Alert, Danger Voted Alarm 1: Actuate on Danger
Voted Alarm 2: Actuate on Alert, Danger Voted Alarm 2: Actuate on Danger
Voted Alarm 3: Actuate on Alert, Danger Voted Alarm 3: Actuate on Danger
Voted Alarms 4 … 12: Not enabled Voted Alarm 4: Actuate on Alert
Voted Alarm 5: Actuate on Alert
Voted Alarm 6: Actuate on Alert
Voted Alarm 7: Actuate on Alert
Voted Alarms 8 … 12: Not enabled
Relay 0 = Module Fault Relay 0 = Module Fault
RELX0 Relay 0 = Voted Alarm 0, on Danger RELX0 Relay 0 = Voted Alarm 0, on Danger
RELX0 Relay 1 = Voted Alarm 1, on Danger RELX0 Relay 1 = Voted Alarm 1, on Danger
RELX0 Relay 2 = Voted Alarm 2, on Danger RELX0 Relay 2 = Voted Alarm 2, on Danger
RELX0 Relay 3 = Voted Alarm 3, on Danger RELX0 Relay 3 = Voted Alarm 3, on Danger
Relay Assigned Output; R = Reserved, NA = Not Allocated
Voted Alarm Instance Voted Alarm Status
Alarm
Status #
0123Voted
Alarm#
01Status to Activate
On
0 1111 14 00 0Fault
1 1000 0 01 2Danger
2 0100 1 01 2Danger
3 1100 2 01 2Danger
4 0010 3 01 2Danger
5 1000 0 10 1Alert
6 0100 1 10 1Alert
7 1100 2 10 1Alert
8 0010 3 10 1Alert
9…12 0000 NA 00 0
Voted Alarm Instance Voted Alarm Status
Alarm
Status #
0123Voted
Alarm#
01Status to Activate
On
0 1000 0 01 2Danger
1 0100 1 01 2Danger
2 1100 2 01 2Danger
3 0010 3 01 2Danger
4 1010 4 10 1Alert
5 0110 5 10 1Alert
6 1110 6 10 1Alert
7 0001 7 10 1Alert
8 …12 0000 NA 00 0