Publication 2711P-UM001B-EN-P
Terminal Connections 6-3
Note 1: AIC+ Module recommended for isolation purposes when PanelView and controller are not on same power
supply
Cables: PanelView Plus to Controller
Protocol PanelView Plus Comm Port
PLC-5, PLC-5C, PLC-5E
CH0 (25-pin RS-232)
(DF1)
ControlLogix
CH0 (9-pin RS-232)
(DF1)
MicroLogix 1000, 1200,
1500LSP
CH0 (8-pin Mini DIN)
(DF1 or DH-485)
DF1
(any)
RS-232 (DF1) Comm Port (9-pin)
PanelView Plus 400 -1500
2711P-RN22C
2711-NC13 (16ft/5m)
2711-NC14 (32ft/10m)
2706-NC13 (10ft/3m)
(9-to-25 pin adapter required)
2711-NC13 (16ft/5m)
2711-NC14 (32ft/10m)
2706-NC13 (10ft/3m)
2711-NC21 (16ft/5m)
2711-NC22 (49ft/15m)
(null modem not required)
** See Note 1 **
DH-485
(any)
RS-232 (DH-485) Comm Port (9-pin)
PanelView Plus 400 -1500
2711P-RN22C
N/A N/A
2711-NC21 (16ft/5m)
2711-NC22 (49ft/15m)
(null modem not required)
** See Note 1 **
DH-485 Communication Port
PanelView Plus 700 -1500
2711P-xxx3x, -xxx6xx, 2711P-RN3, 2711P-RN6
N/A N/A
use AIC+ Module
(1761-NET-AIC)
Connect to Port 3
ControlNet
xxx15xx
ControlNet Communication Port
PanelView Plus 700-1500
2711P-xxx15xx, 2711P-RN15S
to PLC-5C with ControlNet cable
use 1756-CNB Module with
ControlNet cable
N/A
EtherNet/IP
(any except
xx5x)
EtherNet/IP Comm Port
PanelView Plus 400 -1500
(except 2711P-xxx5x)
to PLC-5E
with
Ethernet cable
use 1756-ENET or 1788-ENBT
Module with
Ethernet cable
Use 1761-NET-ENI Module with
Ethernet cable
Remote I/O
xxx1x
xxx6xx
Remote I/O Communication Port
PanelView Plus 400 -1500
2711P-xxx1x, -xxx6xx, 2711P-RN1, 2711P-RN6
shielded twinaxial cable
(1770-CD)
use 1756-DHRIO Module
with
shielded twinaxial cable
(1770-CD)
N/A
DHPlus
xxx6xx
xxx8x
DH+ Communication Port
PanelView Plus 400 -1500
2711P-xxx6xx, -xxx8x, 2711P-RN6, 2711P-RN8
shielded twinaxial cable
(1770-CD)
use 1756-DHRIO Module
with
shielded twinaxial cable
(1770-CD)
N/A
Cables: PanelView Plus to Controller
Protocol PanelView Plus Comm Port
MicroLogix 1500LRP
CH1 (9-pin RS-232)
(DF1 or DH-485)
CompactLogix
CH0 (9-pin RS-232)
(DF1 or DH-485)
FlexLogix
CH0 (9-pin RS-232)
(DF1)
DF1
(any)
RS-232 (DF1) Comm Port (9-pin)
PanelView Plus 400 -1500
2711P-RN22C
2711-NC13 (16ft/5m)
2711-NC14 (32ft/10m)
2706-NC13 (10ft/3m)
DH-485
(any)
RS-232 (DH-485) Comm Port (9-pin)
PanelView Plus 400 -1500
2711P-RN22C
2711-NC13 (16ft/5m)
2711-NC14 (32ft/10m)
2706-NC13 (10ft/3m)
DH-485 Communication Port
PanelView Plus 400 -1500
2711P-xxx3x, -xxx6xx, 2711P-RN3, 2711P-RN6
use AIC+ Module
(1761-NET-AIC)
Connect to Port 3
N/A
ControlNet
xxx15xx
ControlNet Communication Port
PanelView Plus 700-1500
2711P-xxx15xx, 2711P-RN15S
N/A N/A
use 1788-CNC or 1788-CNF Module
with ControlNet cable
EtherNet/IP
(any except
xx5x)
EtherNet/IP Comm Port
PanelView Plus 400 -1500
(except 2711P-xxx5x)
use 1761-NET-ENI Module
with Ethernet cable
use 1788-ENBT Module
with EtherNet cable
Remote I/O
xxx1x
xxx6xx
Remote I/O Communication Port
PanelView Plus 400 -1500
2711P-xxx1x, -xxx6xx, 2711P-RN1, 2711P-RN6
N/A N/A N/A
DHPlus
xxx6xx
xxx8x
DH+ Communication Port
PanelView Plus 400 -1500
2711P-xxx6xx, -xxx8x, 2711P-RN6, 2711P-RN8
N/A N/A N/A
AB Drives

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PanelView Plus 2711P and is the answer not in the manual?

Allen-Bradley PanelView Plus 2711P Specifications

General IconGeneral
BrandAllen-Bradley
ModelPanelView Plus 2711P
CategoryTouch terminals
LanguageEnglish

Related product manuals