Publication 2711P-UM001B-EN-P
2-4 Installation
Clearances
You must allow adequate clearances around the terminal, inside the
enclosure, for adequate ventilation. Consider heat produced by other
devices in the enclosure. The ambient temperature around the
terminals must be between 0…55 °C (32…131 ºF).
Required Tools
Besides the tools required for the panel or enclosure cutouts, you will
need the following for installation:
• small slotted screw driver for securing power and RS-232
connections
• torque wrench (N•m/in-lb) for tightening the mounting clips on
the PanelView Plus 700 - 1500 terminals
Cutout Dimensions
This section provides panel cutout dimensions for each terminal. Use
the full size template shipped with your terminal to mark the cutout
dimensions. All dimensions are in mm (inches).
Clearance 400 - 600 Terminals 700 - 1500 Terminals
Top 51 mm (2 in) 51 mm (2 in)
Bottom 102 mm (4 in) 51 mm (2 in)
Side
(1)
(1)
Maximum side clearance for insertion of memory card and cable wiring is 102 mm (4 in).
25 mm (1 in) 25 mm (1 in)
Back none none
PanelView Plus Terminal Height Width
400 Keypad 123 (4.86) 156 (6.15)
600 Keypad or Keypad & Touch 142 (5.61) 241 (9.50)
600 Touch 123 (4.86) 156 (6.15)
PanelView Plus 700 Keypad or Keypad & Touch 167 (6.57) 264 (10.39)
PanelView Plus 700 Touch 154 (6.08) 220 (8.67)
PanelView Plus 1000 Keypad or Keypad & Touch 224 (8.8) 375 (14.75)
PanelView Plus 1000 Touch 224 (8.8) 305 (12.00)
PanelView Plus 1250 Keypad or Keypad & Touch 257 (10.11) 390 (15.35)
PanelView Plus 1250 Touch 257 (10.11) 338 (13.29)
PanelView Plus 1500 Keypad or Keypad & Touch 305 (12.00) 419 (16.50)
PanelView Plus 1500 Touch 305 (12.00) 391 (15.40)