94 Rockwell Automation Publication 2711P-UM006E-EN-P - January 2017
Chapter 4 Windows CE Operating System
Monitors
The Monitors tab of the PanelView Hardware Monitor provides continuous
voltage, temperature, and load information for the terminal.
Battery Voltage
The Monitors tab gives a visual status and voltage reading of the battery for the
real-time clock. The battery voltage is updated at powerup and then every hour.
Temperatures
The Monitors tab provides a visual status and current temperature of the CPU,
logic board, and terminal display. The temperature is updated every 10 seconds.
Table 51 - Battery Conditions
Condition Logic Module Battery
Depleted Less than 2.0V indicates a dead battery or no power.
Low 2.0…2.74V
Normal 2.75V or higher
Table 52 - Temperature Conditions
Condition Logic Board CPU
(1)
(1) The CPU and display temperatures do not apply to the 400 and 600 terminals.
Display
(1)
Low 10 °C (50 °F) or lower
Normal 25…94 °C (77…201 °F) 25…94 °C (77…201 °F) 11…59 °C (52…138 °F)
High 95 °C (203 °F) and higher 95 °C (203 °F) and higher 60 °C (140 °F) and higher