Programming and Parameters 3-63
Advanced Display Group (continued)
d305 [Speed Feedback F] Related Parameter(s): d304
Displays the value of the actual motor speed (fractional portion) whether measured by encoder/pulse
train feedback or estimated.
Values Default: Read Only
Min/Max: 0.0/0.9
Display: 0.1
d306 [Encoder Speed] Related Parameter(s): d307
32 bit parameter.
Provides a monitoring point that reflects the speed (whole number portion) measured from the
feedback device. This shows the encoder or pulse train speed even if this is not used directly to
control the motor speed.
Values Default: Read Only
Min/Max: 0/64000
Display: 1
d307 [Encoder Speed F] Related Parameter(s): d306
Provides a monitoring point that reflects the speed (fractional portion) measured from the feedback
device. This shows the encoder or pulse train speed even if this is not used directly to control the
motor speed.
Values Default: Read Only
Min/Max: 0.0/0.9
Display: 0.1
d308 [Units Traveled H] Related Parameter(s): d309, E226
32 bit parameter.
Displays the number of user-defined units (whole number portion) traveled from the home position.
Values Default: Read Only
Min/Max: 0/64000
Display: 1
d309 [Units Traveled L] Related Parameter(s): d308, E226
Displays the number of user-defined units (fractional portion) traveled from the home position.
Values Default: Read Only
Min/Max: 0.00/0.99
Display: 0.01