Publication 1747-UM011G-EN-P - June 2008
Setting Up the DH-485 Network 185
1747-UIC USB to DH-485
Interface Converter
The 1747-UIC interface lets you connect DH-485 devices directly to a
computer’s USB port. It features an RS-232 port for connection to
SLC 5/03 and later processors, MicroLogix processor, PanelView 300
and later terminals, 1761-NET-AIC+ interface, and Logix controllers, as
well as an RS-485 port for connection to SLC 5/03 and lower
processors, PanelView 300 and later terminals, and 1747-AIC interface.
The 1747-UIC interface can communicate with devices on the DH-485
network at 19.2 Kbaud.
Connecting to the RS-232 Port
USB (DF1)
RS485 (DH485)
RS232 (DH485)
USB to DH485
INTERFACE CONVERTER
USB
OK
SW
DH485
R
CUS
CAT SER FRN
1747-UIC A X.X
Mfg
XXXX
LISTED IND. CONT. EQ. FOR HAZ.
LOC. A196,
OPERATING TEMP CODE TAG
CLASS 1 GROUPS A, B, C, AND D, DIV. 2
MADE IN INDIA
N223
SLC 5/03, SLC 5/04, SLC 5/05
Processor (channel 0)
PanelView 300 Operator
Interface and later
Personal
Computer with
USB Port
1747-UIC
Interface
AIC+ Interface
ControlLogix Controller
CompactLogix Controller
FlexLogix Controller
MicroLogix Controller
Connect the following DH-485 equipment to
the RS-232 port
Using cable
SLC 5/03, SLC 5/04, and SLC 5/05 processor
(channel 0)
1747-CP3, 1756-CP3
1761-NET-AIC (AIC+)
Advanced Interface Converter
1747-CP3, 1756-CP3 (Port 1, 9-pin D)
1761-CBL-PM02 (Port 2, 8-pin DIN)
PanelView 300 and later operator interface with
RS-232 (DH-485) port
2711-NC13
MicroLogix controller
PanelView 300 Micro (DH-485) operator interface
1761-CBL-PM02
CompactLogix controller 1747-CP3, 1756-CP3
FlexLogix controller 1747-CP3, 1756-CP3
ControlLogix controller 1747-CP3, 1756-CP3