EasyManua.ls Logo

Ametek Sorensen SG Series - Figure 6-2. Power Supply Output for Example 2

Ametek Sorensen SG Series
149 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SCPI Command Operation SG Series Programming
6-48 M550129-03 Rev L
(Notice in this example the sequence is being ended with a RETURN rather than a STOP.
A RETURN is more flexible because it automatically acts like a stop when SEQ2 is run
directly; and yet, if SEQ2 is run as a sub-sequence, then the RETURN shall act as a
statement to return to the calling sequence.)
To run SEQ2 directly, issue the command as before:
OUTP:STAT ON
PROG:STAT RUN
For the running sequence, the power supply output for Example 2 should look like the
following:
Figure 6-2. Power Supply Output for Example 2
Once the ramp goes down to 2 volts, the sequence stops and the unit remains at the state
of the last command within the sequence.
EXAMPLE 3
Issue *RST to establish a known state.
In this third example, redefine SEQ1 so that it calls SEQ2 as a
subroutine.
To modify SEQ1 requires that it be deleted, and re-written. Overwriting a completed,
existing sequence is not allowed by the SCPI command interface for code readability
reasons. Even though overwriting is not permitted, re-writing is permitted after a sequence
has been deleted. Delete the SEQ1 sequence as follows:
PROG:NAME “SEQ1”
PROG:DEL:SEL
That deletes SEQ1.
Now create a new SEQ1 that calls SEQ2 as a subsequence.
PROG:NAME “SEQ1”
PROG:MALL DEFAULT
PROG:DEF 1, VIMODE, 3, 4, 11, 10 //go to 3 volts, 4 amps, 11 volts ovp, for 10 sec
10 volts for 5 sec
Ramp down to 2
volts in 9 sec
Notice that after the RETURN
statement is encountered in this run
of SEQ2, since SEQ2 is being used
as a primary sequence, the RETURN
acts like a STOP statement and stops
running the sequence.

Table of Contents

Related product manuals