Page 13
LOOPSENSE EN54
USER MANUAL
4.8 Disabled Condition
When the user disables an input, output or zone the associated configured outputs will no longer
operate and will no longer effect panel conditions. The system registers a disabled condition as
follows:
Common DISABLED LED will be illuminated
Disabled condition to be reported to the LCD.
The disable event will be logged and printed, where a printer is fitted.
All outputs configured to operate under a disabled condition will operate
<point location> DISABLED
<point descriptor> <type>
<date> <time> CONTROL*
DISABLED XXX OF XXX ◄ZONE
4.9 Other Conditions
The two remaining conditions are:
System
This event is not printed or displayed on the LCD
The event will be logged
All outputs configured to operate under this condition will operate
Transparent
This event is not logged, printed or displayed on the LCD
All outputs configured to operate under this condition will operate