GT3000 STO Function
IMGT30017EN 71
6A.6.5 Installation instructions and extraordinary maintenance
The following instructions apply to start-up, after extraordinary maintenance operations and at least once a year. In order to facilitate
verifications, it is possible to enable the two channels (XM1-20 and XM70-1) separately.
Warning! Qualified personnel, trained on the risks typical of the different operations, shall perform the verifications described below. Keep
away from the hazardous area and prevent access to personnel not tasked with the verification.
Before any operation, check the presence and proper activation of the parking brake in case of vertical or tilted axes.
6A.6.5.1 Controlled Stop
The STO function shall be enabled with the motor stopped, or the uncontrolled stop of the motor must never be dangerous.
In case of controlled stop according to category 1 of EN 60204-1:
1. configure the motor moving at maximum speed and in the most heavy condition for the machine from the stop time standpoint,
2. enable the safety function for the STO request (e.g. opening of the interlocked guard, emergency stop etc.);
3. check that the inverter controls the motor during the deceleration time;
4. check that the controls of the two channels XM1-20 and XM70-1 are disabled (0V) only when deceleration is over and with the
motor stopped;
5. if the interlocked guard is provided with a locking device, make sure that it is released only with the motor stopped;
6. in case of failure of any of the verifications listed in the two items above, check and adjust the automation sequence.
6A.6.5.2 Configuration according to category 3 EN 954-1:
Verification of the faulty restart
1. Enable the “STO request with the motor stopped;
2. make sure that no control of the two channels (XM1-20 and XM70-1) is ON; otherwise, adjust wiring and the automation sequence
and repeat these steps from § 1;
3. verify that the two feedback contacts between terminals XM1-2 and XM1-43 and between terminals XM70-3 and XM70-4 are both
closed: otherwise, replace the safety cards
3
, and repeat these steps from § 1;
4. prepare the drive for motor rotation and make sure that the motor cannot be made revolve: otherwise, replace the safety cards
4
,
and repeat these steps from § 1;
5. repeat the operations described above and enable only 1 channel at a time; make sure that the motor cannot be made revolve;
6. disable the STO function by "increasing" both inputs;
7. make sure that there are no short-circuits in the wiring of feedback contacts; otherwise, repair the fault and restart from § 1;
Failure simulations
8. disable the “STO request; both inputs shall be ”high”;
9. cut-out the connection to the XM1-20 terminal of channel 2 “Drive Enable”;
10. make sure that the control circuit detects the failure of channel 1 “STO”, enabling the “STO alarm procedure in automatic mode and
inhibiting both channels, so that the operating sequence may not be restored up until the failure is removed; otherwise, check the
reasons for non-identification of the failure and proceed accordingly. Restart the verifications from § 1;
11. disable the “STO request, restore the connection to terminal XM1-20 and restore protection devices, if any;
12. cut-out the connection to the XM70-1 terminal of channel 1 “STO”;
13. make sure that the control circuit detects the failure of channel 2 “Drive Enable”, enabling the “STO alarm procedure in automatic mode
and inhibiting both channels, so that the operating sequence may not be restored up until the failure is removed; otherwise, check
the reasons for non-identification of the failure and proceed accordingly. Restart the verifications from § 1;
14. disable the “STO request, restore the connection to terminal XM70-1 and restore protection devices, if any;
15. cut-out the wiring on feed-back contacts’ terminals alternately, enable the STO” function and check the automatic activation of the “STO
alarm procedure, and inhibiting both channels, so that the operating sequence may not be restored up until the failure is removed;
otherwise, check the reasons for non-identification of the failure and proceed accordingly. Restart the verifications from § 1.
6A.6.5.3 CONFIGURATION ACCORDING TO CATEGORY 2 EN 954-1:
1. Enable the “STO request with the motor stopped;
2. make sure that the control of the XM70-1 channel is OFF: otherwise, adjust wiring and the automation sequence, disable the “STO
request and repeat these steps from § 1;
3. make sure that the feedback contact between terminals XM70-3 and XM70-4 is closed: otherwise, replace the safety-related cards
9
,
and repeat these steps from § 1;
4. make sure that the motor cannot be made revolve: otherwise, replace the safety-related cards
10
, and repeat these steps from § 1;
5. disable the STO function by “increasing the signal entering the XM70-1 terminal;
6. make sure that there are no short-circuits in the wiring of the feedback contact; otherwise, repair the failure and restart from § 1;
Failure simulation
7. disable the “STO request;
8. cut-out the conductor connection to the XM70-3 or XM70-4 terminal;
9. enable the “STO request;
3
According to the instructions mentioned in the relevant specification.
4
According to the instructions mentioned in the relevant specification.
9
According to the instructions mentioned in the relevant specification.
10
As above.