The burner output is modulated varying the
VENTILATOR rpm between the minimum to the
maximum speed.
The burner runs until the scale prevention
temperature is reached. The temperature is
checked by the sanitary probe NTC return.
Performed from the flow and return NTC. If the
temperature rise 102°C a lock out occurs,
indicated on the display with 1 01.
To reduce the formation of scale in the secondary
exchanger.
During the D.H.W. mode the switch off and switch
on of the burner depends on the following values of
temperature:
N.B.: The sanitary switch-off logic could be changed by the parameter 2 53:
– 0 : Anti-scale (62 or 65°C) default