Training manual ALTEAS & GENUS ONE
Page. 82 of 88 Version 2V2.
9.3.6 Menù 7 : Zone module
Zone 1 pump control
(set parameter 710 =1)
0: Off
1: On (timed 10 min)
Zone 2 pump control
( set parameter 710 =1)
0: Off
1: On (timed 10 min)
Zone 3 pump control
( set parameter 710 =1)
0: Off
1: On (timed 10 min)
Zone 2 mix valve control
( set parameter 710 =1)
0: Off
1: Open (timed o 10 min)
2: Close (timed 10 min)
Zone 3 mix valve control
( set parameter 710 =1)
0: Off
1: Open (timed 10 min)
2: Close (timed 10 min)
0: not defined
1: MCD
2: MGM II
3: MGM III
4: MGZ I
5: MGZ II
6: MGZ III
ΔT between zone delivery and
boiler delivery (°C)
0 ÷ 40
(0= ΔT varible according the number of
zones that require heat; HT = +7°C
each zone; LT = +5°C each zone)
0: Heat request (to do a heat request to
a generic boiler)
1: External pump management
2: Alarm (the contact close if there is an
error regarding the zone module)
External temperature correction
YES: push button “OK”
NO: push button “ESC”
Reset menu 7 factory setting
YES: push button “OK”
NO: push button “ESC”