Training manual ALTEAS & GENUS ONE
Page. 36 of 88 Version 2V2.
There is one bi-colour led (green and red) in the frontal part of the pump:
Led off: pump off or not supplied;
Led green on fix: pump on with stable speed;
Led green on blinking: pump on with speed changing;
Led red on fix: pump blocked; with the system empty or with air inside the system switch-on alternatively
the red led and the green blinking.
With the PWM wire disconnected (main PCB connector CN10) the pump goes at the maximum speed.
5.3.1 Types of post-circulation
3 min
(set by parameter 237
beetwen 0 e 15’)
Heating Off by Summer/Winter
button
3 min
(set by parameter 237
beetwen 0 e 15’)
NTC return > 62°C or 67°C
Par. 254=0 30 sec
if:Tdel<75°C ; 3 min
if Tdel>75°C;
Post circulation: 30sec
End of antifreeze function
End of chimney sweeping
function
Pressure sensor (102), Low
pressure (108, 111)
No circulation (103, 104, 105,
106, 107)
Flame missing, flame lift
(501, 504)
Overheat (101), Thermo fuse
opening (610)
No circulation (1P1, 1P2, 1P3)
Floor thermostat opened (116)