6.7.2 CO2 adjustment - minimum power
Switch on the boiler at the minimum power (using
“FLUE CLEANER” function Min power)
Wait till the value of the CO2 on the exhaust
analyser is stable.
Compare the CO2 value with the values in the table
below.
If the CO2 value is not ok press “OK” button and the
display shows the adjustment bar.
Using the buttons “<” and “>” to adjust the CO2
value (it is possible modify the CO2 of a value
±0,5%).
Note: To see the CO2 variation it needs to finish
this procedure and perform 5 ignitions of the
boiler.
To save the new setting push the button “Ok”
N.B.: Values with casing closed.