9.3.5 Menù 6 : Zone 3 parameters
Pump fixed speed setting (with
par. 540 = 0)
Temperature setpoint zone 3
Select high or low temperature
for zone 3
0: low temperature
1: high temperature
Thermoregulation mode
selection
0: fixed delivery temperature
1: basic thermoregulation
2: only room probe
3: only outside probe
4: room probe + external probe
Select thermoregulation curve
0_2 ÷ 1_0 (par. 420=0)
1_0 ÷ 3_5 (par. 420=1)
(with Auto function enabled)
0_6 (par 420=0)
1_5 (par 420=1)
Select thermoregulation curve
parallel shifting
-7 ÷ 7 (par. 420=0)
-14 ÷ 14 (par. 420=1)
(with Auto function enabled )
Influence of the room probe on
thermoregulation
0 ÷ 20
(with Auto function enabled )
Zone 3 maximum heating
temperature (°C)
20 ÷ 45 (par. 420=0)
35 ÷ 82 (par. 420=1)
45 (par. 420=0)
82 (par. 420=1)
Zone 3 minimum heating
temperature (°C)
20 ÷ 45 (par. 420=0)
35 ÷ 82 (par. 420=1)
20 (par. 420=0)
35 (par. 420=1)
Zone 3 delivery temperature
(°C)
Zone 3 return temperature (°C)
Heating request by zone 3
OFF: no
ON: yes
(only visualization)
OFF: switch-off
ON: switch-on
(only visualization)
ZONE 3 ZONE MODULE SETTINGS (visible only with zone module connected)
0: Fix
1: Modulating (ΔT)
2: Modulating (pressure)
7 (par. 420=0)
20 (par. 420=1)
Pump fixed speed setting (with
par. 640 = 0)