ADR141A /
ADR241A
Ref ID : ADR241A/IM/UG
Rev No. : 02
steps of 1%.
Setting the HF value to 00 will bypass the
instantaneous element.
Press the Left arrow key () to move to the next option.
IP> Curve = C1
Range C1 – C6
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the desired IP> Curve can be selected.
Seven different types of curves are provided C1 to C6.
When the given value is C1 curve 1 is selected and when
the given value C2 curve 2 is selected.
Curve Description
C1
Normal Inverse 1 (10 Times 3.0 sec)
C2
Normal Inverse 2 (10 Times 1.3 sec)
C3
Very Inverse (10 Times 1.5 sec)
C4
Extremely Inverse (10 Times 0.8 sec)
C4A
Extremely Inverse (10 Times 0.6 sec)
C5
Long Time Inverse (10 Times 13.3 sec)
C6
Definite Time (Inst. to 99.9 sec)
Press the Left arrow key () to move to the next option.
IE> Curve = C1
Range C1 – C6
Editable Setting
By using the Plus / Up arrow key (+ /) or the Minus / Down
arrow key (- /) the desired IE> Curve can be selected.
Seven different types of curves are provided C1 to C6.
When the given value is C1 curve, 1 is selected and when
the given value C2 curve 2 is selected.
Curve Description
C1
Normal Inverse 1 (10 Times 3.0 sec)
C2
Normal Inverse 2 (10 Times 1.3 sec)
C3
Very Inverse (10 Times 1.5 sec)
C4
Extremely Inverse (10 Times 0.8 sec)
C4A
Extremely Inverse (10 Times 0.6 sec)
C5
Long Time Inverse (10 Times 13.3 sec)
C6
Definite Time (Inst. to 99.9 sec)