‘Service Timer’
‘Running Hours’
‘hrs’ 2130
‘Menu’
F1 F2 F3
• The screen shows the actual running hours.
• Press the tabulator key (2): a screen similar to the one below will appear:
‘Service Timer’
‘Level A’
‘hrs’ 4000
‘Menu’ ‘Mod.’
F1 F2 F3
• The screen indicates that the level for ‘Service Plan’ A is set at 4000 running hours.
• Press the ‘Mod.’ key (F2). The key ‘Lim’ (F2) can be used to find out the limitations for the
parameter. Use the arrow up and arrow down keys to modify the interval.
• Press the ‘Prog’ key (F1) to program the new setting or the ‘Canc’ key (F3) to cancel the
modification operation.
• The procedure to modify the Service plans B, C and D is similar.
3.17 Programming clock function
Control panel
Function
To program:
• Time-based start/stop commands for the compressor
• Time-based change-over commands for the net pressure band
Programming start, stop and pressure band commands
In this example, the compressor will be programmed as follows:
• On Monday at 06:15 starting in ‘Press Band 1’
• On Friday at 18:00 changing over to ‘Press Band 2’
• On Saturday at 18:00 stopping
Instruction book
API161475 33