Hardware Installation Manual 38 Document #: LTRT-10236
Mediant 800 MSBR
2. Connect a cable with LC-type plugs to the SFP transceivers (labeled GE SFP).
Figure 5-6: Cabling Fiber-Optic WAN GbE Port – Mediant 800B MSBR
Figure 5-7: Cabling Fiber-Optic WAN GbE Port – Mediant 800C MSBR
5.2.3 SHDSL WAN Cabling
Each SHDSL port provides up to four wire-pairs, which can support up to two RJ-11
physical connectors.
Warnings:
• The device does not include primary telecom protection! When the DSL telephone
lines are routed outside the building, additional protection - usually a 350V three-
electrode Gas Discharge Tube (GDT) as described in ITU-T K.44 - must be provided
at the entry point of the telecom wires into the building (usually on the main
distribution frame / MDF), in conjunction with proper grounding. The center pin of the
GDT (MDF grounding bar) must be connected to the equipotential grounding bus bar
of the Telecommunication room.
• To protect against electrical shock and fire, use a minimum 26-AWG wire to connect
the DSL ports.
Note: SHDSL is applicable only to Mediant 800B MSBR.
SHDSL port specifications:
Conforms to ITU G.991.2 Annexes A, B, E, F and G SHDSL
Up to 5,696 Kbps over a single wire pair
Up to 22,784 Kbps over four wire pairs bonding, according to SHDSL.bis (ITU G.991.2