11.3. Maintenance
Lubrication
In the factory, the gear housing is filled with grease.
Grease change is performed during maintenance
- Generally after 4 to 6 years for modulating duty.
- Generally after 6 to 8 years if operated frequently (open-close duty).
- Generally after 10 to 12 years if operated rarely (open-close duty).
We recommend exchanging the seals when changing the grease.
No additional lubrication of the gear housing is required during operation.
Notes regarding the
maintenance
Check actuator visually. Ensure that no outside damage or changes are visible.
The electric connection cables must be without damage and wired correctly.
Thoroughly touch up any possible damage to painting to prevent corrosion. Original
paint in small quantities can be supplied by AUMA.
Cable entries, cable glands, plugs etc. have to be checked for correct tightness
and sealing. Consider torques according to manufacturer's details. If required, re-
place the components. Only use components which are approved for use in haz-
ardous locations.
Check whether Ex connections are fastened correctly.
Take care of possible discoloration of the terminals and wires.This would indicate
an increased temperature.
For Ex housings, pay special attention to a possible collection of water. This may
originate from condensation due to severe temperature variations (e. g. change of
night and day), from damaged seals etc. Remove any water immediately.
Check the flame path gaps of flameproof enclosures for dirt and corrosion.
Since the dimensions of all flameproof joints are strictly defined and inspected, no
mechanical work (such as grinding) shall be performed on them. The flameproof
joints should be cleaned suitably.
Prior to fitting, preserve joint surfaces with an acid-free corrosion protection agent
(e. g. Esso Rust-BAN 397).
Ensure that all housing covers are handled carefully and that the seals are checked.
All cable and motor protection components have to be checked.
If defects impairing the safety are detected during maintenance, repair measures
have to be initiated without delay.
Any kind of surface coating for the flameproof joints is not permitted.
When exchanging parts, seals etc. only original spare parts shall be used.
11.4. Disposal and recycling
AUMA devices have a long lifetime. However, they have to be replaced at one point in
time.The devices have a modular design and may, therefore, easily be separated and
sorted according to materials used, i.e.:
electronic scrap
various metals
plastics
greases and oils
The following generally applies:
Greases and oils are hazardous to water and must not be released into the environ-
ment.
Arrange for controlled waste disposal of the disassembled material or for separate
recycling according to materials.
Observe the national regulations for waste disposal.
45
SAEx 07.2 SAEx 16.2 / SAREx 07.2 SAREx 16.2
Servicing and maintenance

Table of Contents

Other manuals for AUMA SAEx 07.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SAEx 07.2 and is the answer not in the manual?

AUMA SAEx 07.2 Specifications

General IconGeneral
BrandAUMA
ModelSAEx 07.2
CategoryController
LanguageEnglish

Related product manuals