6 Parameter Settings and Functions     
64    © Copyright Reserved Autonics Co., Ltd. 
6.4.3  Alarm output option 
Select the desired alarm output option mode. 
AL-A  Standard alarm 
If it is an alarm condition, alarm output is ON. Unless an alarm 
condition, alarm output is OFF. 
AL-B  Alarm latch
※1
 
If it is an alarm condition, alarm output is ON. Before reset the 
alarm, an ON condition is latched. (Holding the alarm output)   
AL-C 
Standby 
sequence 1
※2
 
When power is supplied and it is an alarm condition, alarm 
output does not act. From the second alarm conditions, 
standard alarm acts. 
AL-D 
Alarm latch 
and standby 
sequence 1 
When power is supplied and it is an alarm condition, alarm 
output does not act. From the second alarm conditions, alarm 
latch acts.   
AL-E 
Standby 
sequence 2 
When Standby sequence
※3
 and it is an alarm condition, alarm 
output does not act. After deactivate the alarm condition, 
standard alarm acts. 
AL-F 
Alarm latch 
and standby 
sequence 2 
When Standby sequence
※3
 is repeated and it is an alarm 
condition, alarm output does not act. After deactivate the alarm 
condition, alarm latch acts. 
※1.  Alarm Latch: Deactivating Alarm Output in Alarm Latch mode: Turn off the power or send 
alarm reset signal. 
※2. Standby sequence: This option is applied only if PV is in alarm output ON conditions when 
power is supplied. If not, alarm output will be provided from the first alarm condition same 
as other alarm operations.   
※3. Conditions of repeated Standby sequence: Power ON, Changing SV, Related 
Alarm(operation mode, option, setting value), Changing Parameter, Changing STOP mode 
to RUN mode. 
Setting group  Parameter  Setting range  Factory default  Unit 
Alarm Setting  Alarm Type 
Refer to the 
above table. 
AL-A  - 
 
  You can set alarm output (Alarm 1 Type to Alarm 4 Type) individually. 
  If alarm output mode has been selected as LBA, SBA or HBA, AL-C, AL-D modes are not 
available.