36 Avocent PM PDU Installer/User Guide
To assign outlet access for a new custom user group:
NOTE: Assigning outlet access to user groups allows group members to turn outlets on or off, and enable locking
and power cycle capabilities on compatible PDUs.
1. Click Users - Authorization - Groups.
2. Click on the new user group name.
3. In the Side Navigation Bar, click Access Rights
- Power - Outlets.
4. Click Add.
The Add Outlet screen is displayed.
5. For connected PDUs, click the Select PDU button to activate the
Connected PDUs and Outlets
fields.
6. Select Connected PDU from
the pull-down menu.
7. Enter the outlets assigned to the us
er group.
NOTE: Outlets can be specified individually, (for example 1,3,6,8) or as a range (for example 1-4) or a
combination of both, (for example 1-4,6,8 which assigns access to outlets 1, 2, 3, 4, 6 and 8).
8. If a custom PDU ID has been created for future use, and you want to pre-assign outlets, click
the Custom button to enter the custom PDU ID name and specify the outlets.
9. Click Save.
T
o assign appliance access rights for custom user groups:
1. Click Users - Authorization - Groups.
2.
Click the new user group name.
3. In the Side Navigation Bar, click Access
Rights - Appliance.
4. Select the desired appliance access rights and click Save.
Event and Logs
The PM PDU will generate notifications for a wide variety of events. You can configure it to direct
or store those event notifications to various destinations for immediate use or for analysis later.
Event List
The Event List screen lists PM PDU events, each of which can be configured for SNMP Traps,
Syslog, DSView 3 software, Email and SMS.
To configure Events:
1. Click Events
and Logs - Events.
2. Locate the events for which you wa
nt notification sent and select the checkbox(es) next to the
event number(s).
3. Click Edit.