A-2
Guide 
number
Display Reading Item Remarks
2-6
70.0
Input %
Displays the item value in 
percentage.
INPUT Input Signal
2-7
70.1
Opening 
(Reverse transduction 
of flow amount 
characteristic)
Displays the item value in 
percentage.
POS Position
2-8
O_TYP
Single-acting/
double-acting
Output Type
SINGLE (single-
acting) 
DOUBLE (double-
acting)
SINGLE: Single-acting 
DOUBLE: Double-acting 
Set during auto setup. 
(Initial setting: SINGLE)
2-9
P_ACT
Forward/reverse
Positioner Action
DIRECT (forward) 
REVERSE
 
(reverse)
DIRECT: Forward 
REVERSE: Reverse 
Set during auto setup. 
(Initial setting: DIRECT)
2-10
15.3
Angle when the 
valve opening is 0%
Displays the item value in 
degrees.
0%.DEG 0% angle (Degree)
2-11
13.2
Angle when the 
valve opening is 0%
Displays the item value in 
degrees.
100%.DEG 100% angle (Degree)
2-12
701
Basic model 
number 
_ _ _ of basic model number 
AVP_ _ _
MODEL Basic model number 
Status monitor
Guide 
number
Display Reading Item Remarks
3-1
SS_00
Status
SS: StatusSummary 
Numerical value: Status category
0x01
0x: Hexadecimal format 
Numerical value: Details of status