A-4
Guide
number
Display Reading Item Remarks
8-3
AJ100
(AJ 0)
ADJ adjustment
angle selection
AJ100 : Adjust 100% Angle
(AJ 0 : Adjust 0% Angle)
COARSE→
MID →
FINE →
Angle adjusted by operating
the button once
COARSE : 1°
MID : 0.1°
FINE : 0.01°
8-4
97.5
ADJ is being
adjusted
Valve opening (%)
AJ100%
(AJ 0%)
AJ100% : Adjust 100% Angle
(AJ 0% : Adjust 0% Angle)
8-5
99.8
ADJ monitor
Valve opening (%)
235.0kPa Output air pressure OUT1
8-6
ST 0
ST100
ADJ Manual
Setting
adjustment
opening selection
ST 0 : Set 0% angle
ST100 : Set 100% angle
→
8-7
ST 0
ST100
Waiting until ADJ
Manual Setting is
performed
ST 0 : Set 0% angle
ST100 : Set 100% angle
OK?→→
To perform manual setting,
hold down the
button.
8-8
ST 0
ST100
ADJ Manual
Setting completed
ST 0 : Set 0% angle
ST100 : Set 100% angle
SUCCESS
Supply bypass
Guide
number
Display Reading Item Remarks
9-1
BPS
BPS initial screen
Supply Bypass
60s
Time until the setup mode
automatically ends
(Not displayed if the time is
longer than 60 seconds.)
9-2
BPS
BPS pressure
selection
Supply Bypass
: P_MIN→→
: P_MAX→→
To perform the selected
supply bypass, hold down the
button.
9-3
BPS
BPS execution
Supply Bypass
: RUN_MIN
: RUN_MAX
Flashes.