2-13
5) Piping
Use piping with an inside diameter of 6 mm.
When using the device in a corrosive atmosphere, select piping appropriate to the
environment of the installation location. For example, you may use the vinyl-coated
copper pipe.
To prevent air leaks, be sure to use a fitting that is appropriate for the pipe.
6) Connection positions
The positions of the supply air connection port and output air connection port are shown
in the figure below. Select the dimensions of the connection port screws according to the
specifications.
Rc1/4 or 1/4NPT
Output air connection port (OUT1)
Supply air connection port (SUP)
Output air connection port (OUT2)
(For double-acting actuator)
Rc1/4 or 1/4NPT
Figure 2-15 Pneumatic Piping Connection
Handling Precautions:
When connecting the electromagnetic valve for emergency shutoff, air
valve, or other part, install it between the output air connection and the
actuator rather than the supply air connection side of the device.