5-9
Message
LUI display 
example *1
LUI display
Description and cause Action
Upper 
part
Lower part  
[*: Optional]
Po Validity + 
Alarm
― ―
The output air pressure 
validity + is larger than 
the threshold value.
Check the operation of 
the control valve.
Po Validity - 
Alarm
― ―
The output air pressure 
validity - is smaller than 
the threshold value.
Check the operation of 
the control valve.
Max Friction 
Alarm
― ―
The maximum friction is 
larger than the threshold 
value.
Check the operation of 
the control valve.
Stick-Slip 
High Alarm
― ―
Stick-slip is larger than the 
“High” threshold value.
Check the operation of 
the control valve.
Stick-Slip 
Medium 
Alarm
― ―
Stick-slip is larger than 
the “Medium” threshold 
value.
Check the operation of 
the control valve.
Stick-Slip 
Low Alarm
― ―
Stick-slip is larger than 
the “Low” threshold value.
Check the operation of 
the control valve.
Deviation + 
Alarm
― ―
The deviation + is larger 
than the threshold value.
Check the operation of 
the control valve.
Deviation - 
Alarm
― ―
The deviation - is smaller 
than the threshold value.
Check the operation of 
the control valve.
Zero Travel 
+ Alarm
― ―
The zero point opening 
+ is larger than the 
threshold value.
Check the operation of 
the control valve.
Zero Travel - 
Alarm
― ―
The zero point opening 
- is smaller than the 
threshold value.
Check the operation of 
the control valve.
Travel Cutoff 
High
― ―
The valve was forcibly 
fully opened.
Check the forced fully 
open and closed values 
and apply the input signal 
within the setting range.
Travel Cutoff 
Low
― ―
The valve was forcibly 
fully closed.
Factory 
Settings 
Restored
― ―
The data set when the 
device was shipped from 
the factory was restored.
The factory data restoration 
(Restore factory settings) 
operation was performed.
Perform appropriate 
adjustment and setup.
In Use by an 
Operator
― ―
Settings are being 
changed through HART 
communication or with the 
LUI.
Check who the operator 
is that is changing the 
settings.