5-8
Message
LUI display 
example *1
LUI display
Description and cause Action
Upper 
part
Lower part  
[*: Optional]
Temp Low 
Alarm
AL_16 0x08,0x09,0x0A
The internal temperature 
is lower than the 
specified threshold value.
- Check the ambient 
temperature.
- Check that the threshold 
value is appropriate for 
the usage environment.
Restriction 
is clogged
AL_04 0x01
The EPM drive signal 
has exceeded the normal 
operation range.
- The fixed diaphragm is 
clogged.
- Air is not supplied.
- The valve shaft is 
galled.
- Clean the fixed flow 
restriction.
- Check the supply air 
pressure.
- Check the EPM drive 
signal.
- Change the input signal 
to confirm seamless 
operation.
(- Perform auto setup.)
Deposits on 
the Nozzle-
Flapper
AL_04 0x02
The EPM drive signal 
has exceeded the normal 
operation range.
- The nozzle is clogged.
- The A/M switch is in 
manual mode.
- Clean the nozzle.
- Check that the A/M 
switch is in auto mode.
- Check the EPM drive 
signal.
- Change the input signal 
to confirm seamless 
operation.
Total Stroke 
Alarm
― ―
The cumulated sliding 
distance is larger than 
the threshold value.
Check the operation of 
the control valve.
Cycle Count 
Alarm
― ―
The number of inversion 
operations is larger than 
the threshold value.
Check the operation of 
the control valve.
Shut Count 
Alarm
― ―
The number of fully 
closing operations is 
larger than the threshold 
value.
Check the operation of 
the control valve.
Max Tvl 
Speed + 
Alarm
― ―
The maximum operation 
speed + is larger than the 
threshold value.
Check the operation of 
the control valve.
Max Tvl 
Speed - 
Alarm
― ―
The maximum operation 
speed - is smaller than 
the threshold value.
Check the operation of 
the control valve.