5-7
Message
LUI display 
example *1
LUI display
Description and cause Action
Upper 
part
Lower part  
[*: Optional]
Input Signal 
Low
AL_03
0x*2,0x*3,0x*6,0x*7
0x*A,0x*b,0x*E,0x*F
The input current is too 
low.
Input at least 3.5mA
Insufficient 
Input Signal 
Range
AL_03
0x*4,0x*5,0x*6,0x*7
0x*c,0x*d,0x*E,0x*F
The input signal range is 
too narrow.
Set the input signal span 
more than 2mA.
Temperature 
Out of 
Range
AL_03
0x*8,0x*9,0x*A,0x*b
0x*c,0x*d,0x*E,0x*F
The temperature in the 
device is lower than -40° 
or higher than 80°.
Set the ambient 
temperature to between 
-40° and 80° as specified 
by the usage conditions. If 
this message is displayed 
even though this condition 
is satisfied, a sensor error 
is suspected. Contact 
Azbil group.
Supply 
Pressure 
Out of 
Range
AL_03 0x1*,0x5*
The supply air pressure 
detected in the device 
is lower than 50 kPa or 
higher than 715 kPa.
- Check that the supply air 
pressure is applied.
- Set the supply air 
pressure to 715 kPa or 
lower. If this message 
is displayed even 
though this condition is 
satisfied, a sensor error 
is suspected. Contact 
Azbil group.
Incorrect 
Setting of 
Input Range 
High/Low
AL_03 0x4*,0x5*
The high and low setting 
of the input signal range 
are incorrect.
Make sure the sttings 
of Input Range High 
(Open)and Input Range 
Low (Closed).
Supply 
Pressure 
High Alarm
AL_16 0x01,0x05,0x09
The supply air pressure 
is higher than the 
specified threshold value.
- Check the supply air 
pressure.
- Check that the threshold 
value is appropriate.
Supply 
Pressure 
Low Alarm
AL_16 0x02,0x06,0x0A
The supply air pressure 
is lower than the 
specified threshold value.
Temp High 
Alarm
AL_16 0x04,0x05,0x06
The internal temperature 
is higher than the 
specified threshold value.
- Check the ambient 
temperature.
- Check that the threshold 
value is appropriate for 
the usage environment.