5-6
■ PV input range low limit/high limit setup
(1) In the operation display mode, keep the [para] key
pressed for 2 sec. or longer.
>> The unit then enters the parameter setting mode.
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 sec. or longer.
>> The display is then changed to the setup setting
display.
(3) Press the [para] key several times.
>> Display the setup setting, [C05: PV input range low
limit] or [C06: PV input range high limit].
(4) Press the [<], [], or []key to change the set value
in [C05] or [C06].
Setting range:
-1999 to +9999 (no decimal point)
-199.9 to +999.9 (1 digit after decimal point)
-19.99 to +99.99 (2 digits after decimal point)
-1.999 to +9.999 (3 digits after decimal point)
>> When no keys are pressed for 2 sec. or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>> The display is returned to the operation display.
The following describes the relationship between the PV input and PV when
setting up the range low limit and high limit:
Handling Precautions
When the input type of the model is “L: DC current or DC voltage”,
[C05: PV input range low limit] and [C06: PV input range high limit] can
be set. When the input type is “T: Thermocouple” or “R: RTD”, the
setup item is displayed, but the set value cannot be changed.