Chapter 11. SPECIFICATIONS
11-1
■ Specifications
● PV input
Thermocouple: K,J,E,T,R,S,B,N (JIS C1602-1995)
PL II (Engelhard Industries Data (ITS90))
WRe5-26 (ASTM E988-96(Reapproved 2002))
DIN U,DIN L (DIN 43710-1985)
Resistance temperature
detector (RTD): Pt100 (JIS C1604-1997)
JPt100 (JIS C1604-1989)
DC voltage: 0 to 1V, 1 to 5V, 0 to 5V, 0 to 10V
DC current: 0 to 20mA, 4 to 20mA
Sampling cycle time: 500ms
Indication accuracy:
±0.5%FS±1digit, ±1%FS±1digit in the negative area of the thermocouple.
±0.5%FS±2digits, or ±1%FS±2digits in the negative area if the
thermocouple range is displayed with a decimal point (Specified by the
input conversion at an ambient temperature of 23±2˚C)
However, the accuracy of the B-thermocouple is ±5%FS at a temperature
of 260˚C or less and ±1%FS at a temperature of 260 to 800˚C.
If ROM version 1 of the instrument information bank (Id02) is prior to
2.04, the value is -180˚C.
PV bias: -1999 to +9999 or -199.9 to +999.9
• T/C input
Input bias current: +0.2µA (Flowed from the A terminal.)
Burnout indication: Upscale + AL01
Thermocouple or
compensating wire: 0.3 to 0.65mm diameter
Allowablr input voltage
: -0.5 to +12V
Note: When the dedicated loader cable is connected to the SDC15, the temperature characteristics of the
controller may be affected, but control is not.
• RTD input
Input bias current: Approx. +1mA (Flowed from the A terminal.)
Burnout indication: RTD burnout or A-wire burnout
. . . . .
Upscale + AL01
B-wire burnout or C-wire burnout
. . .
Upscale + AL01, AL03
2 or more wires burnout
. . . . . . . . . . .
Upscale + AL01, AL03
Allowable wiring resistance: 10Ω or less for range No.51 to 64
85Ω or less for range other than above range
Effect of wiring resistance: Max. ±0.05%FS/Ω
• DC voltage input
Input impedance: Min. 1MΩ
Input bias current: 0 to 1V range
. . . . . . . . . . . . . . . . . . . .
1µA (sucked to the A terminal)
0 to 5V, 1 to 5V range
. . . . . . . . . . . . .
3.5µA (sucked to the A terminal)
0 to 10V range
. . . . . . . . . . . . . . . . . . .
7µA (sucked to the A terminal)
Burnout indication: Downscale + AL02
However, the burnout cannot be detected in a range of 0 to 10V.
• DC current input
Input impedance: Max. 100Ω
Burnout indication: Downscale + AL02
However, the burnout cannot be detected in a range of 0 to 20mA.
Allowable input current: Max. 30mA
Allowable input voltage: Max. 4V (a higher voltage might cause device failure)