11-2
Chapter 11. SPECIFICATIONS
● Control output
• Relay output
Output rating: Control output 1 NO side 250Vac/30Vdc, 3A (resistance load)
Control output 2 NC side 250Vac/30Vdc, 1A (resistance load)
Life: 50,000 cycles or more on NO side
100,000 cycles or more on NC side
Min. open/close specifications: 5V, 100mA
Min. open time
close time: 250ms
• Voltage pulse output (For SSR drive)
Open voltage: 19Vdc±15%
Internal resistance: 82Ω±0.5%
Allowable current: Max. 24mAdc
OFF leak current: Max. 100µA
Min. OFF time/ON time: 1ms when the time proportional cycle time is less than 10s.
250ms when the time proportional cycle time is more than 10s.
• Current output
Output type: 0 to 20mAdc or 4 to 20mAdc (current output)
Allowance load resistance: Max. 600Ω
Output accuracy: ±0.5%FS (under standard conditions)
However, ±1.0%FS in a range of 0 to 1mA.
● Event relay output
Number of output points: 0 to 3 points (This may vary depending on the model.)
Output type: SPST contact 3 points, Common 2 points, Each individual point
Output rating: 250Vac/30Vdc, 2A (Resistance load)
Service life: 100,000 cycles or more
Min. open/close specifications: 5V, 10mA (Reference value)
● Digital input
Number of input points: 2 points
Input type: No-voltage contact or open collector
Allowable ON contact resistance: Max. 250Ω
Allowable OFF contact resistance: Min.100 kΩ
Allowable ON-state residual voltage: Max. 1.0V
Open terminal voltage: 5.5Vdc ± 1V
ON terminal voltage: Approx. 7.5mA (at short-circuit), Approx. 5.0mA (at contact
resistance of 250Ω)
Minimum hold time: 1s or more
● Current transformer input
Number of input points: 2 points
Input object: Current transformer with 100 to 4,000 turns (availability is by
100-turn units)
Optional unit Model No.:
QN206A* (800 turns, hole diameter: 5.8 mm)
Optional unit Model No.:
QN212A* (800 turns, hole diameter: 12mm)
* Not UL-certified.
Current measurement lower limit: 0.4Aac (800 turns, 1 time)
Formula; Number of turns ÷ (2000 x number of power wire loops)
Current measurement upper limit: 50.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of power wire loops)
Allowable measured current: 70.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of power wire loops) x 1.4