EasyManuals Logo

Azbil SDC15 User Manual

Azbil SDC15
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #134 background imageLoading...
Page #134 background image
11-2
Chapter 11. SPECIFICATIONS
Control output
• Relay output
Output rating: Control output 1 NO side 250Vac/30Vdc, 3A (resistance load)
Control output 2 NC side 250Vac/30Vdc, 1A (resistance load)
Life: 50,000 cycles or more on NO side
100,000 cycles or more on NC side
Min. open/close specifications: 5V, 100mA
Min. open time
close time: 250ms
• Voltage pulse output (For SSR drive)
Open voltage: 19Vdc±15%
Internal resistance: 82±0.5%
Allowable current: Max. 24mAdc
OFF leak current: Max. 100µA
Min. OFF time/ON time: 1ms when the time proportional cycle time is less than 10s.
250ms when the time proportional cycle time is more than 10s.
• Current output
Output type: 0 to 20mAdc or 4 to 20mAdc (current output)
Allowance load resistance: Max. 600
Output accuracy: ±0.5%FS (under standard conditions)
However, ±1.0%FS in a range of 0 to 1mA.
Event relay output
Number of output points: 0 to 3 points (This may vary depending on the model.)
Output type: SPST contact 3 points, Common 2 points, Each individual point
Output rating: 250Vac/30Vdc, 2A (Resistance load)
Service life: 100,000 cycles or more
Min. open/close specifications: 5V, 10mA (Reference value)
Digital input
Number of input points: 2 points
Input type: No-voltage contact or open collector
Allowable ON contact resistance: Max. 250
Allowable OFF contact resistance: Min.100 k
Allowable ON-state residual voltage: Max. 1.0V
Open terminal voltage: 5.5Vdc ± 1V
ON terminal voltage: Approx. 7.5mA (at short-circuit), Approx. 5.0mA (at contact
resistance of 250)
Minimum hold time: 1s or more
Current transformer input
Number of input points: 2 points
Input object: Current transformer with 100 to 4,000 turns (availability is by
100-turn units)
Optional unit Model No.:
QN206A* (800 turns, hole diameter: 5.8 mm)
Optional unit Model No.:
QN212A* (800 turns, hole diameter: 12mm)
* Not UL-certified.
Current measurement lower limit: 0.4Aac (800 turns, 1 time)
Formula; Number of turns ÷ (2000 x number of power wire loops)
Current measurement upper limit: 50.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of power wire loops)
Allowable measured current: 70.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of power wire loops) x 1.4