INTRODUCTION
I-E96-508C D - 1
APPENDIX D - MODULAR POWER SYSTEM SIZING TABLES
INTRODUCTION
The tables in this appendix enable you to size the modular
power system and bypass the calculations required by the siz-
ing procedure in Appendix B. Use Table D-1 to size power sys-
tems that have only IEPDS01 and IEPDS02 modules. To use
the tables, first determine the current requirements for the
cabinet (refer to Appendix B). Shown in the table are values for
A (5 VDC current requirement for the cabinet) and B (24 VDC
current requirement for the cabinet). The box intersected by
the requirements of A and B shows the number of PDS mod-
ules needed.
Table D-1. Q1 for Systems Using IEPDS01/02 Modules Only
A
B
024681012141618202224262830
0
0112233445566778
5
1122334455667788
10
1122334455667788
15
2223344556677889
20
2223344556677889
25
3333445566778899
30
3333445566778899
35
44444556677889910
40
44444556677889910
45
555555667788991010
50
555555667788991010
55
6666666778899101011
60
6666666778899101011
65
77777777889910101111
70
77777777889910101111
75
888888888991010111112
80
888888888991010111112
85
9999999999101011111212
90
9999999999101011111212
95
10 10 10 10 10 10 10 10 10 10 10 11 11 12 12 13
100
10 10 10 10 10 10 10 10 10 10 10 11 11 12 12 13