Device description
4.2 Functions
5290 / 06/2023 en BENNING PV 1-1+ 21
4.2.4 Error messages
Code Meaning Remedial measure
FUSE The built-in fuse is defective. Replace the fuse of the device
[}page41].
HOt The electronic components of
the device have reached the
maximum admissible
temperature. The functioning
of the device is restricted until
the device has cooled down.
Disconnect the device from the
object to be measured and let
it cool down.
HiSC The DC short-circuit current
has exceeded the maximum
value of 15A. Measurement
has been cancelled.
Carry out the measurement
within the admissible
measuring range.
HiOC The DC open-circuit voltage
has exceeded the maximum
value of 1 000V. Measurement
has been cancelled.
CAL The device is defective. Please return the device to an
authorised service center
[}page9].
Er1, 2 etc.
HOtF
FEt
rL1, 2, 3 or 4
EEPro Switch the device off an on
again. If the error persists,
return the device to an
authorised service center
[}page9].
rF
Table6: Error messages
4.2.5 BENNINGSUN2
The insolation and temperature measuring instrument BENNINGSUN2 is an optional
accessory and can send the following measured values to the device via radio transmission:
• Insolation (W/m²)
• PVmodule temperature
• Ambient temperature
• Date and time stamp
Indications on the digital display of the device
• Within radio range, the measured insolation value(W/m²) is displayed.
• Outside the radio range, the “W/m²” flashes.
• Outside the insolation measuring range, the “---”symbol is displayed.
Synchronising the date and time
If the device is in radio communication with the BENNINGSUN2 and detects a deviation of
more than 1minute for the date and time, the device will automatically adopt the date and time
of the BENNINGSUN2 after approx. 10seconds.
BENNINGSUN2 (primary) → BENNINGPV1‑1 (secondary)