Chapter 9 – RS485/Modbus RTU Communications
9-8
9.5.2 SGoperatingstatusinAddressE,Commonarea
Output frequency
Forward Run command
Reverse Run command
Accelerating
Decelerating
Speed arrival
Stopping
Stop
Forward running
Reverse running
< Address usage area by groups >
DRV 9100 - 91FF
FUN 9200 – 92FF
AFN 9300 – 93FF
I/O 9400 - 94FF
EXT 9500 - 95FF
COM 9600 - 96FF
APP 9700 - 97FF
Address setting method to access the parameter using Modbus: area assigned by inverter+ Address usage area by
groups + Code no. (Hex).
Ex) To check the content of I/O-93 [COM Time Out]; perform Read or Write of address 0x945D.