Chapter 5 – Parameter List
5-15
PARAM Description
LCD Keypad
Display
Setting Range
Factory
Default
Adj.
During
Run Page
I/O-90 Inverter Number
Inv No.
1 - 250 1 Yes
6-57
I/O-91 Baud Rate Selection
Baud rate
1200 bps
9600 Yes
2400 bps
4800 bps
9600 bps
19200 bps
38400 bps
I/O-92
Operating method
at loss of frequency reference
COM Lost Cmd
None
None Yes 6-57
FreeRun
Stop
I/O-93
Loss of Communication
Delay Time
COM Time Out
0.1 - 120 sec 1.0 Yes 6-57
I/O-94
Communication Response
Delay time
Delay Time
2 - 1000 msec 5 Yes 6-57
I/O-95 A or B contact
In No/Nc Set
00000000000
11111111111
0 No 6-58
I/O-96 Input time
In CheckTime
1 - 1000 msec 1 No
6-58
I/0-97 Overheat trip selection
OH Trip Sel
000 - 111 bit 010 No
6-58
I/0-98
Motor overheat trip
temperature
MotTripTemp.
0 - 255 ℃
110 No
The gray-highlighted parameters are hidden parameters and will appear when the related functions
are set.
Note 24: When DRV-04 and/or DRV-92 are set to either V1, V1S, I, V1+I, or Pulse only selected
parameters are displayed in I/O-01~I/O-19.
Note 25: I/O-35 ~ I/O-42 displayed only when one of I/O-20 ~ I/O-27 is set to Speed_X.
Note 26: I/O-52 ~ I/O-63 displayed only when one of I/O-20 ~ I/O-27 is set to either XCEL_L, XCEL_M,
XCEL_H.
Note 27: When Process PI Control is selected with APP-02, select units with I/O-86 and the maximum
value of the units with I/O-87. See also APP-06, APP-31, APP-32 and APP-33.