EasyManua.ls Logo

BIFFI IMVS2000v2 - Section 13: Trouble Shooting

BIFFI IMVS2000v2
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
September 2019
Installation, Operation and Maintenance Manual
MAN720_IMVS2000v2_IOM Rev. 6
MAN720_IMVS2000v2_IOM Rev. 6
Section 13: Trouble Shooting
Trouble Shooting
Section 13: Trouble Shooting
WARNING
If the device is located in hazardous area a ‘’hot permit’’ must be obtained before opening the explosion
proof enclosures. Moreover, the area must be cleaned from explosive mixture since batteries and power
supply could generate electrical spark and cause explosion.
WARNING
During the opening and closing the IMVS2000v2 units, pay attention do not damage the joint surface
of the covers.
Table 17.
# Detected problem Actions to be performed
1 THE IMVS DOES NOT SWITCH ON WHEN POWERED
verify the Main Supply on terminals 3 & 4.
verify that the wiring is correct.
verify the Display Card cable is connected.
2 THE IMVS DOES NOT WORK FROM LOCAL CONTROLS
verify the integrity of the Display Card cable.
Device already connected to Biffi Assistant.
3 THE IMVS CAN NOT MOVE THE ACTUATOR
verify the wiring is correct.
verify the pneumatic or hydraulic connections.
verify the supply on terminals 5-6 and 12-13
(if connected).
verify the supply pressure of the actuator.
4 NO OUTPUT VOLTAGE TO THE SOLENOID VALVE(S)
verify that the wiring is correct.
verify the supply on terminals 5-6 and 12-13
(if connected).
verify that the voltage on terminals 8-9-10 and
16-17-18 respects the polarity (±).
verify that available power (Watts) of power supply
source is correctly sized.
5
THE LOCAL POSITION INDICATOR IS NOT CONSISTENT
WITH ADHESIVE LABEL
remove the base cover (see 10).
remove the position indicator (just pull the item to
disassembly from the position sensor).
rotate the position indicator 90 degrees.
install again the cover and tighten the screws.
6
THE IMVS DOES NOT IDENTIFY CORRECT TRAVEL
LIMITS OR ACTUATOR POSITION
perform a Calibration.
verify the mechanical coupling of the IMVS to the
actuator: no clearance must exist.
7 THE IMVS GETS NO PRESSURE INDICATION
verify the tubing between IMVS and actuator.
verify the supply pressure of the actuator.
8 THE IMVS CAN NOT PERFORM THE BASELINE PST
verify the Main Supply on terminals 3 & 4.
verify that the wiring is correct.
verify the supply on terminals 5-6 and 12-13.
(if connected)
verify that the voltage on terminals 8-9-10 and
16-17-18 respects the polarity. (±)
verify that “Base. S. St.” = “Passed.
verify that “PST En.” = “Yes.
8 THE IMVS CAN NOT PERFORM THE BASELINE SIGNATURE
verify the Main Supply on terminals 3 & 4.
verify that the wiring is correct.
verify the supply on terminals 5-6 and 12-13.
(if connected)
verify that the voltage on terminals 8-9-10 and
16-17-18 respects the polarity. (±)
verify the pneumatic or hydraulic connections.
verify the supply pressure of the actuator.
verify that “Cal. Status” = “Passed.
verify that “Sign. En.” = “Yes.”
102

Table of Contents

Related product manuals