EasyManua.ls Logo

BIFFI IMVS2000v2 - Page 23

BIFFI IMVS2000v2
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation, Operation and Maintenance Manual
September 2019
MAN720_IMVS2000v2_IOM Rev. 6
Section 5: Working Principle
Working Principle
The SOV TEST can be performed by using a dedicated input (SOLENOID B CONTROL) or a dedicated
parameter (RL B CMD).
The SOV TEST is executed only on to the SOV B.
The SOV B is not involved in the other commands of the IMVS2000v2 (Calibration, Signatures and PST),
for these commands the SOV A is used.
In this configuration:
SOV A is used for the PST
SOV B is just used for its own SOV TEST.
The SOV TEST can be performed only if a Baseline PST is already successfully done.
See Errore. L'origine riferimento non è stata trovata. for details.
3. Configuration Z
Act. Mode” = “Single” or “Double-S”
“SOVs Qty” = “Simplex”
“PST Ser. SOVs = “One”
“Pr. S. 1-2” ≠ “None
“PST En. = “No
“PST Pos. %” = 0.0%
“PST Pres. %” = 0%
“PST Time %” = 0%
Al. PSA En. ≠ “No”
4. Configuration T
Act. Mode” = “Single” or “Double-S”
“SOVs Qty” = “Series
“PST Ser. SOVs = “Both”
“Pr. S. 1-2” ≠ “None”
“PST En. = “No”
“PST Pos. %” = 0.0%
“PST Pres. %” = 0%
“PST Time %” = 0%
Al. PSA En. ≠ “No”
Al. PSB En. ≠ “No”
The SOV TEST can be performed by using a dedicated input (PST CONTROL) or the dedicated
parameters (BASELINE PST CMD or MANUAL PST CMD).
The SOV TEST is executed on both solenoid valves and it can be completed only if a Baseline Signature
is already successfully done.
This configuration is available from Logic Card FW Rev. 1.00.01
This configuration is available from Logic Card FW Rev. 1.00.01.
See Section 10 for details.
19

Table of Contents

Related product manuals